Infrared thermometer , Flue gas analyser
 
9888
FLUE GAS ANALYSIS



 
Infrared thermometer , Flue gas analyser
Specifications
O2 measurement
Sensor: Electrochemical
Measurement range: 0...20.9 vol. %
Accuracy: 0.3 vol. % absolute
CO indicator (not H2 compensated)
Sensor: Semiconductor
Measurement range: 0...350 ppm
Accuracy: 50 ppm
CO Sensor (not H2 Compensated)
Sensor: Electrochemical
Measurement range: 0...3,000 ppm
Accuracy: ± 5 % o.r ± 20 ppm
Inlet air temperature measurement-TA
Measurement range: 0...99.9°C with TF probe
Accuracy: 2°C: 0...50°C
opt. (for measurements accord. to pollution control regs.)
Measurement range: -20.0...99.9°C with TA probe
Accuracy: 1°C: 0...50°C
Flue-gas temperature measurement - TF
Measurement range: 0...800°C
Accuracy: 2°C: 0...125°C
3 °C: 125...250 °C
4 °C: 250...400 °C
Chimney draught, DP
Measurement range: -100...+4,000 Pa
Accuracy: 3 Pa: -20...100 Pa
3 % FSD: -1.0...4.0 hPa
CO2 determination
Display range: 0...CO2max
Resolution: 0.1 %
Flue-gas loss determination - qA
Depending on fuel, resolution 0.1%
Efficiency - h
Display range: 0...120.0 %
Resolution: 0.1 %

Dewpoint temperature measurement
Depending on fuel, resolution 0.1°C
Condensate quantity
Display in kg/m³ (gas) or kg/l (oil)

E 98 Advanced Set, Plastic Case with printer
for determination of O2, CO2, CO, Flue Gas Temmperature, Combustion Air Temperature, Dew Point, Chimney Pressure, Flue Gas Loss, Lambda, and Efficiency.

NEW! Now TÜV approved according EN 50 379, part 2!

Advantages
Optionally with measurement data memory for ten sets of measurement data and IR interface for printing out data and permanent data transmission
Optionally with 1.7 m hose
Additional pressure connection for gas pressure adjustments or differential pressure measurements
Reacts quickly due to extremely short gas paths
Versatile in operation with dry or rechargeable batteries
Long operating period: e.g. 38 hours of operation with Mignon dry cells (2.3 Ah) or 10 hours with standard NiCd rechargeables (600 mA)
Gas treatment section can be dismantled completely for cleaning
Rugged due to well-designed gas treatment section with integral, easily replaceable water stop filter

Applications
Adjustments on oil and gas-fired heating systems
Replaces your vibrating-bottle analyser and does much more

Comes with
E 98 IR with measurement data memory and IR interface
protective sleeve
set of rechargeable NiCd batteries
combustion air temperature probe 280 mm
TD600 fast thermal printer
charger A 97 / E 98
plastic case
PTFE cone
E 98 replacement kit