Infrared thermometer, Flue gas analyser
 
9908
FLUE GAS ANALYSIS



 
Infrared thermometer, Flue gas analyser
Specifications
O2 measurement
Sensor: Electrochemical
Measurement range: 0...20.9 vol. %
Accuracy: 0.3 vol. % absolute
CO indicator (not H2 compensated)
Sensor: Semiconductor
Measurement range: 0...350 ppm
Accuracy: 50 ppm
CO Sensor (not H2 Compensated)
Sensor: Electrochemical
Measurement range: 0...3,000 ppm
Accuracy: ± 5 % o.r ± 20 ppm
Inlet air temperature measurement-TA
Measurement range: 0...99.9°C with TF probe
Accuracy: 2°C: 0...50°C
opt. (for measurements accord. to pollution control regs.)
Measurement range: -20.0...99.9°C with TA probe
Accuracy: 1°C: 0...50°C
Flue-gas temperature measurement - TF
Measurement range: 0...800°C
Accuracy: 2°C: 0...125°C
3 °C: 125...250 °C
4 °C: 250...400 °C
Chimney draught, DP
Measurement range: -100...+4,000 Pa
Accuracy: 3 Pa: -20...100 Pa
3 % FSD: -1.0...4.0 hPa
CO2 determination
Display range: 0...CO2max
Resolution: 0.1 %
Flue-gas loss determination - qA
Depending on fuel, resolution 0.1%
Efficiency - h
Display range: 0...120.0 %
Resolution: 0.1 %

Dewpoint temperature measurement
Depending on fuel, resolution 0.1°C
Condensate quantity
Display in kg/m³ (gas) or kg/l (oil)

E 98 Maxi CO Professional Set, Aluminium Case with printer
for determination of O2, CO2, CO, Flue Gas Temmperature, Combustion Air Temperature, Dew Point, Chimney Pressure, Flue Gas Loss, Lambda, and Efficiency.

With electrochemical CO sensor up to 3,000 ppm

NEW! Now TÜV approved according EN 50 379, part 2!

Advantages
with measurement data memory for ten sets of measurement data and IR interface for printing out data and permanent data transmission
with 1.7 m hose
Additional pressure connection for gas pressure adjustments or differential pressure measurements
Reacts quickly due to extremely short gas paths
Versatile in operation with dry or rechargeable batteries
Long operating period: e.g. 38 hours of operation with Mignon dry cells (2.3 Ah) or 10 hours with standard NiCd rechargeables (600 mA)
Gas treatment section can be dismantled completely for cleaning
Rugged due to well-designed gas treatment section with integral, easily replaceable water stop filter

Applications
Adjustments on oil and gas-fired heating systems
Replaces your vibrating-bottle analyser and does much more

Comes with
E 98 Maxi CO with electrochemical CO sensor up to 3,000 ppm
integrated data memory and IR interface
flue-gas probe 295 mm, 1.7 m cable-hose
rubber boot E 98
clamping cone
PTFE cone
charger A 97/E 98
set of rechargeable batteries
TD600 fast thermo printer with 10 rolls of thermo paper
RP 72 soot test pump set
combustion air temperature probe 280 mm with 1.6 m cable
magnetic holder
3 pcs. water stop filter
150 pcs. wadding rolld
spare part kit E 98
aluminium case